Electrical installation
Cable specification
7
96
EDBMB935X DE/EN/FR 13.0
7.2 Cable specification
ƒ The cables used have to comply with the requirements on the location
(e. g. EN 60204−1).
ƒ The corresponding minimum cross−sections of the cables have to be
observed.
ƒ Only use shielded cables with a braid of tinned or nickel−plated copper.
Shields of steel braid are unsuitable.
The overlap rate of the braid has to be at least 70 % with an overlap
angle of 90 °.