Commissioning
Addressing
5
EDKMF2133 DE/EN/FR 6.1
61
H2 Adressierung−SetSlaveAdress
Addressing
Every device connected to the bus must get an unambiguous address.
Note!
ƒ If S1 − S7 = OFF, the configurations set under code C0009 will become active
when the device is switched on.
ƒ If S1 ... S7 = ON, the configurations of all switch positions will become active
when the device is switched on.
The Lenze setting for the switches (S1 − S8) is OFF.
Switch off the voltage supply of the communication module and switch it on
again to activate the changed settings.
Valid address range: 3 126
(Lenze setting: 126, if C0009 = 1)
The address can be set arbitrarily
ƒ using the front switch (62)
ƒ the keypad or PC (63) or
ƒ through the master (class 2) (63)