Lenze EPM−T9XX Modular system Instrukcja Użytkownika Strona 364

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 544
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 363
Parameterising 2/4xcounter module
Encoder with G/RES (modes 28 ... 30)
12
Parameter setting via system bus (CAN) / CANopen
12.4
12.4.15
L
12.4−44
EDSPM−TXXX−9.0−11/2009
The counter is incremented by 1 on
l a LOW−HIGH edge at input IN2 / IN5 (A) and a LOW level at the input
IN3 / IN6 (B).
l a HIGH−LOW edge at input IN2 / IN5 (A) and a HIGH level at input
IN3 / IN6 (B).
l a LOW−HIGH edge at input IN2 / IN5 (A) and a HIGH level at input
IN3 / IN6 (B).
l a HIGH−LOW edge at input IN2 / IN5 (A) and a LOW level at the input
IN3 / IN6 (B).
epm−t152
Fig. 12.4−61 Signal characteristic of 2/4xcounter in the mode 30 (upcounter)
The counter is decremented by 1 on
l a LOW−HIGH edge at input IN2 / IN5 (A) and a HIGH level at input
IN3 / IN6 (B).
l a HIGH−LOW edge at input IN2 / IN5 (A) and a LOW level at the input
IN3 / IN6 (B).
l a LOW−HIGH edge at input IN2 / IN5 (A) and a LOW level at the input
IN3 / IN6 (B).
l a HIGH−LOW edge at input IN2 / IN5 (A) and a HIGH level at input
IN3 / IN6 (B).
epm−t153
Fig. 12.4−62 Signal characteristic of 2/4xcounter in the mode 30 (downcounter)
Signal characteristic in mode 30