MA_p500 DE/EN/FR/ES/IT 2.0
2
UL_Warn_p500-M-Install_WiHis_p500
Approval
Underwriter Laboratories (UL), UL508 and CSA C22.2 No. 142-M1987, (UL File Number
E236341)
Ratings
ƒ Input24VDC,max.1.7A
ƒ Max. Surrounding temperature:
P500 7: 55 °C, in vertical (landscape or portrait) mounting position only at relative
humidity of 60%rh with a linear derating to 30°C at 90%rh.
P500 10,4: 55°C in vertical (landscape or portrait)mounting position only at a
relative humidity of 55%rh with a linear derating to 40°C at 90%rh.
P500 15,0: 55°C in vertical (landscape or portrait)mounting position only at a
relative humidity of 45%rh with a linear derating to 40°C at 90%rh.
ƒ These devices are intended for mounting in the outer surface of an enclosure, Type 1,
4 and 4X indoor use only.
Warnings!
Field Wiring Markings
Wiring Terminal MSTB 2,5/3-STF-5,08:
ƒ Use 60° or 60/75° C copper wire only.
ƒ AWG 18 ... AWG 12 (0.82 mm
2
... 3.3 mm
2
)
ƒ Torque 5...7 lb-in (0.5 ... 0.6 Nm)
Device
ƒ For use in a pollution degree 2 and controlled environment only.
ƒ For use on a Flat Surface of a Type 1, 4 and 4x Indoor Use Only Enclosure
Optional filed bus module
ƒ Use only together with appropriate cable connectors, provided with screws
for securement and secure connector to avoid loosening.