TCF SeriesInstallation and Operation Manual

Strona 2

4 TCF SPECIFICATIONSSpecification RangeStorage Temperature -20° to 70° CAmbient Operating Temperature 0° to 50° C (derate 2.5% per °C above 50°) Amb

Strona 3 - Table of Contents

5 TCF RATINGSMODELNUMBER(NOTE 1)FOR MOTORSRATEDINPUT (50-60 Hz) OUTPUTHEAT LOSS(WATTS)(NOTE 5)INPUTPHASECURRENT(AMPS)POWER(kVA)CURRENT(AMPS)HP kWTF20

Strona 4 - Safety Information

MODELNUMBER(NOTE 1)FOR MOTORSRATEDINPUT (50-60 Hz) OUTPUTHEAT LOSS(WATTS)(NOTE 5)INPUTPHASECURRENT(AMPS)POWER(kVA)CURRENT(AMPS)HP kWTF400 SERIES (NOTE

Strona 5 - 1 GENERAL

6 INSTALLATIONNOTETCF Series drives are intended for inclusion within other equipment, by professional electrical installers according to E

Strona 6 - 1.6 CUSTOMER MODIFICATION

6.1 INSTALLATION AFTER A LONG PERIOD OF STORAGESTOP!Severe damage to the drive can result if it is operated after a long period of storage or inactiv

Strona 7 - 2 TCF DIMENSIONS

7 INPUT AC POWER REQUIREMENTSDANGER!Hazard of electrical shock! Capacitors retain charge after they've been removed. Disconnect incom

Strona 8 - MODEL H W D P R

7.2 INPUT FUSING & DISCONNECT REQUIREMENTSA circuit breaker or a disconnect switch with fuses must be provided in accordance with the National El

Strona 9 - 3 TCF MODEL DESIGNATION CODE

7.3 INPUT WIRE SIZE REQUIREMENTSINPUT WIRE SIZE REQUIREMENTS208/240 Vac, 1 phase 208/240 Vac, 3 phase 400/480 Vac, 3 phase 480/590 Vac, 3 phaseMODEL

Strona 10 - 4 TCF SPECIFICATIONS

8 POWER WIRINGDANGER!Hazard of electrical shock!Capacitors retain charge after power is removed. Disconnect incoming power and wait until

Strona 11 - 5 TCF RATINGS

9 TCF POWER WIRING DIAGRAMTHREE PHASE INPUT(ALL SERIES)L1 L2 L3OUTPUT (ALL SERIES)3 PHASEAC MOTORDC BUSVOLTAGET1 T2 T3 B- B++SINGLE PHASE INPUT(TF200

Strona 13 - 6 INSTALLATION

10 CONTROL WIRING10.1 CONTROL WIRING VS. POWER WIRINGExternal control wiring MUST be run in a separate conduit away from all other input

Strona 14

10.5 SPEED/TORQUE REFERENCE SIGNALSSPEED POT Connect the wiper of the speed pot to terminal TB-5, and the high and low leads to terminals TB-6 and T

Strona 15 - 7.1 INPUT VOLTAGE RATINGS

WARNING!When operating in JOG mode, the STOP signal and the AUXILIARY STOP function (Parameters 10-12) WILL NOT stop the drive. To stop the

Strona 16

10.7 ANALOG OUTPUT SIGNALSTerminal TB-30 can provide a 0-10 VDC or a 2-10 VDC signal proportional to output frequency, load, or torque.

Strona 17

11 TCF CONTROL WIRING DIAGRAMS11.1 TCF TERMINAL STRIPThe following diagram represents the terminal strip on the main control board and provides a br

Strona 18 - 8 POWER WIRING

11.2 TWO-WIRE START/STOP CONTROLThis wiring diagram shows a typical two-wire start/stop control scheme, using one maintained contact (such as that fr

Strona 19 - 9 TCF POWER WIRING DIAGRAM

11.3 ALTERNATE TWO-WIRE START/STOP CONTROLThis wiring diagram shows an alternate two-wire start/stop control scheme, using one maintained contact for

Strona 20 - 10 CONTROL WIRING

11.4 THREE-WIRE START/STOP CONTROLThis wiring diagram shows a typical three-wire start/stop control scheme, using momentary contacts (such as push-bu

Strona 21

11.5 SPEED POT AND PRESET SPEED CONTROLThis wiring diagram illustrates SPEED POT and/or PRESET SPEED control with a two-wire start/stop circuit.MAINT

Strona 22

11.6 BIPOLAR SPEED CONTRO L (-10 to +10 VDC)The three wiring diagrams herein provide examples of using a -10 to +10 VDC bipolar speed reference.SIGNA

Strona 23 - 10.7 ANALOG OUTPUT SIGNALS

Table of Contents1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strona 24 - 11.1 TCF TERMINAL STRIP

12 INITIAL POWER UP AND MOTOR ROTATIONDANGER!Hazard of electrical shock!Capacitors retain charge after power is removed. Disconnect incoming

Strona 25

Follow the procedure below to check the motor rotation. This procedure assumes that the drive has been powered up for the first time, and that none of

Strona 26

13 PROGRAMMING THE TCF DRIVEThe drive may be programmed by one of three methods: using the three buttons and 3-digit LED display on the front of the

Strona 27

Use the s and t buttons to scroll to the desired parameter number. In the example below, Parameter 19 is displayed. Parameter 19 is the ACCELERATION T

Strona 28

The TCF Series drive contains two or three sets of parameter values, depending on whether the drive has been programmed with optional OEM default sett

Strona 29

13.2 TCF DRIVE PERSONALITYEach TCF model has a unique "personality" (voltage and HP). This information is stored in the EPM, and is also pe

Strona 30 - Apply input power

14 PARAMETER MENUNO. PARAMETER NAME RANGE OF ADJUSTMENTFACTORYDEFAULT(NOTE 1)01 LINE VOLTAGE HIGH (01), LOW (02) HIGH (01)02 CARRIER FREQUENCY 2kHz (

Strona 31

NO. PARAMETER NAME RANGE OF ADUSTMENTFACTORYDEFAULT(NOTE 1)11TB-13B FUNCTION SELECTNONE (01), 0-10 VDC (02), 4-20 mA (03),NONE (01)PRESET SPEED #2 (04

Strona 32 - password value

NO. PARAMETER NAME RANGE OF ADJUSTMENTFACTORYDEFAULT(NOTE 1)28 FIXED BOOST 0.0 - 30.0 % 1.0 %29 ACCEL BOOST 0.0 - 20.0 % 0.0 %30 SLIP COMPENSATION 0.0

Strona 33

NO. PARAMETER NAME RANGE OF ADJUSTMENTFACTORYDEFAULT(NOTE 1)57 TB STRIP STATUS (VIEW-ONLY) (N/A)58 KEYPAD STATUS (VIEW-ONLY) (N/A)59 TB-30 OUTPUT (VIE

Strona 34

TCF Sub-Micro DriveINPUT POWERTERMINALSOUTPUT(MOTOR)TERMINALSCONTROL TERMINALSTRIP3-DIGIT LED DISPLAYELECTRONICPROGRAMMINGMODULE (EPM)PROGRAMMINGBUTTO

Strona 35 - 13.2 TCF DRIVE PERSONALITY

15 DESCRIPTION OF PARAMETERSP01 LINE VOLTAGE SELECTIONThis calibrates the drive for the actual applied input voltage, and can be set to HIGH (01) or

Strona 36 - 14 PARAMETER MENU

P03 START METHODWARNING!Automatic starting of equipment may cause damage to equipment and/or injury to personnel! Automatic start should on

Strona 37 - (NOTE 1)

P04 STOP METHOD01 COAST TO STOP: When a STOP command is given, the drive shuts off the output to the motor, allowing it to coast freely to a stop.02

Strona 38

05 FAULT LOCKOUT: Closes when input power is applied. Opens if three restart attempts are unsuccessful, or if input power is removed.06 AT SET SPEED

Strona 39

P08 TB-30 ANALOG OUTPUTTerminal TB-30 can be used as an analog output proportional to output frequency, load or motor torque.01 NONE Disables TB-30 O

Strona 40 - 15 DESCRIPTION OF PARAMETERS

11 AUXILIARY STOP: When TB-13A is opened with respect to TB-4, the drive will decelerate to a STOP (even if STOP METHOD is set to COAST) at the rate

Strona 41

P12 TB-13C FUNCTION SELECTThis selects the function of terminal TB-13C. Closing TB-13C to TB-4 (or opening in the case of setting 06) activates the s

Strona 42

P13 TB-15 OPEN COLLECTOR OUTPUTThis selects the status indication for the open-collector output at TB-15, and has the same selections as Parameter 6

Strona 43

P17 ROTATION DIRECTION01 FORWARD ONLY: The drive will only allow rotation in the forward direction. However, JOG REVERSE (Parameter 12) will still o

Strona 44

NOTEIf either the Minimum Frequency or Maximum Frequency parameter is changed while the drive is running, the new value will not take effect

Strona 45

1 GENERAL1.1 PRODUCTS COVERED IN THIS MANUALThis manual covers the Lenze AC Tech TCF Series Variable Frequency Drive.1.2 PRODUCT CHANGESLenze AC Te

Strona 46

P28 FIXED BOOSTFIXED BOOST is active only in V/Hz mode (refer to Parameter 80), and increases starting torque by increasing the output voltage when

Strona 47

Refer to the table herein for activation of the preset speeds using the TB-13 terminals.SPEED # TB - 13A or 13D TB - 13B TB - 13C1 CLOSED OPEN OPEN2 O

Strona 48

P39 SPEED SCALINGThis scales the display to indicate speed or user units other than frequency. This parameter should be set to the desired display va

Strona 49

P44 PASSWORDThis allows the PASSWORD to be changed to any number between 000 and 999. Setting PASSWORD to 000 disables the password function.NOTEThe

Strona 50 - 3 1.5% 10 1.0%

P48 PROGRAM SELECTIONThis is used to select whether the drive will operate according to the user settings or the optional OEM default setti

Strona 51

P49 TB-13D FUNCTION SELECTThis selects the function of terminal TB-13D. Closing TB-13D to TB-4 (or opening in the case of settings 06 and 09) activat

Strona 52

P51 SOFTWARE VERSIONThis displays the software version number for the control board software. This information is useful when contacting the factory

Strona 53

P58 KEYPAD AND PROTECTION STATUSThis indicates the status of the buttons on the keypad and the status of the protective circuitry in the drive, using

Strona 54

04 ENHANCED VARIABLE V/Hz: Achieves maximum performance for variable torque applications. This setting may be required for high inertia fan applicati

Strona 55

P83 CURRENT LOOP I GAINNormally, this parameter should not require adjustment. In special cases, however, it may need to be adjusted to

Strona 56

INSTALLATIONEnsure proper handling and avoid excessive mechanical stress. Do not bend any components and do not change any insulation distances

Strona 57 - CURRENT

P92 MOTOR INDUCTANCEThis will be automatically adjusted when the AUTO CALIBRATION (Parameter 81) function is performed. Once the AUTO CALIBRATION fun

Strona 58

16 TROUBLESHOOTING To aid in troubleshooting, Parameters 50 through 59, 73, 95 and 96 can be accessed without entering the PASSWORD (Parameters 95 an

Strona 59

FAULT MESSAGESFAULT DESCRIPTION & POSSIBLE CAUSESAd A/D converter offset error - consult factory. AF High Temperature Fault: Ambient temperature i

Strona 60

17 TCF DISPLAY MESSAGES The following describes the various displays and messages that can appear on the TCF drive.17.1 SPEED/TORQUE DISPLAYIf the

Strona 61 - 16 TROUBLESHOOTING

17.2 CHANGING THE SPEED REFERENCE SOURCEWhen the speed/torque source is changed while the drive is running, the display will flash the message for the

Strona 62

17.3 STATUS AND WARNING MESSAGESSTATUS AND WARNING MESSAGESDISPLAY DESCRIPTIONbr DC BRAKING The DC braking circuit is activated.CAL CALIBRATION The A

Strona 63 - 17 TCF DISPLAY MESSAGES

A APPENDIX - VECTOR MODEA.1 GENERALThe TCF Series is a sensorless vector drive that can be operated in speed or torque mode, as well as V/Hz mode. O

Strona 64

A.3 ENHANCED V/Hz MODEIn cases where Vector mode is not appropriate, the TCF Series drive can be operated in Enhanced V/Hz mode to achieve maximu

Strona 65 - DISPLAY DESCRIPTION

B APPENDIX - INPUT ASSERTION LEVELB.1 GENERALDigital inputs on VFDs are asserted or activated by either applying a voltage level to the input (activ

Strona 66 - A APPENDIX - VECTOR MODE

B.3 PROCEDURE FOR CHANGING INPUTS FROM ACTIVE-HIGH TO ACTIVE-LOWIf it is necessary to change the assertion level from active-high to active-low, it c

Strona 67

2 TCF DIMENSIONSMounting Tab DetailIf R < 6.30" (160)S = 0.19" (5)T = 0.38" (10)U = 0.18" (5)V = 0.66" (17)If R = 6.30&qu

Strona 68 - TCF DIGITAL INPUT (+12 VDC)

B.3.2 PROCEDURE #2 - USING THE EPM PROGRAMMER1. Remove power from the drive.2 Remove all control wiring from the terminal strip of the drive.3. Us

Strona 69

B.4 ASSERTION LEVEL AND THE EPMThe TCF drive will store the setting of Parameter 79 - INPUT ASSERTION LEVEL on the EPM (like it does with all o

Strona 70

B.5 DESCRIPTION OF ASSERTION LEVEL FAULTSAlong with the "A1" fault described above, there are a few other faults associated with the drive&

Strona 71

NOTES69

Strona 72

NOTES70

Strona 74

Lenze AC Tech Corporation630 Douglas Street • Uxbridge, MA 01569 • USASales: 800 217-9100 • Service: 508 278-9100www.lenzeamericas.comDocument: TF01D-

Strona 75

HP kWINPUT VOLTAGEMODEL H W D P R0.5 0.37208 / 240 TF205Y 5.75 (146) 2.88 (73) 3.94 (100) 0.80 (20) 4.37 (111)400 / 480 TF405 5.75 (146) 3.76 (96) 5.2

Strona 76 - Lenze AC Tech Corporation

3 TCF MODEL DESIGNATION CODEThe TCF model number gives a full description of the basic drive unit.EXAMPLE: TF210Y = TCF Series, 208/240 Vac, 1 HP, si