Lenze · PLC Designer | Migration of V2.x projects · 1.2 EN - 02/2013 13
General information
Control configuration
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4. The wildcard describes a program:
$Program$.bToggle ??PLC_PRG.bToggle
This type of wildcard replacement cannot be imported into the »PLC Designer« V3.x. (This
wildcard replacement is only used in exceptional cases.)
5. The wildcard is replaced by different types:
$Var$
Replacement 1 : PLC_PRG.n (INT)
Replacement 2 : PLC_PRG.st (STRING)
Remedy: Two different wildcards must be defined in the interface.
6. The visualisation is in a library. The wildcards will be replaced later from any project.
Remedy 1: The TYPE_NONE data types must be replaced manually.
Remedy 2: The library must be implemented into a project and the wildcard must be replaced
correctly. If this project is then imported, the data type is determined correctly in the library
as well.
Grouping
Groups and (not yet) available elements cannot
be imported into the »PLC Designer« V3.
5.3 Control configuration
The control configuration of a »PLC Designer« V2 project cannot be imported into the »PLC Desig-
ner« V3.
As a consequence...
the device configuration must be created anew .
the variables in the control configuration must be declared anew.
5.4 Network variables
In the »PLC Designer« V3.x, GVL objects are created. The variable declarations can be imported.
The network properties are not
imported.
5.5 Access to the CANopen master or CANopen slave
The access to internal variables of the CANopen master/CANopen slave (e.g. nStatus) via the
global data structures existing in the »PLC Designer«< V2 project is not
possible in the »PLC Desig-
ner« V3.
The access takes place in the »PLC Designer« V3 via function calls of the CiA405 library (new in
V3).
5.6 L-force Motion
5.6.1 AxisGroup not available anymore
The axis groups used in »PLC Designer« V2 are not available in V3.