Configuration
8200SHB0199
7-73
7.7.4 Motor-phase failure detection
Only series “HVAC
Setting range 821X: not possible
Setting range 822X/824X:
Code Name
Possible settings
IMPORTANT
Lenze Choice Info
C597*¤ Activation of
motor-phase failure
detection
-0- -0- Inactive
-1- TRIP
-2- Warning
C599 Current limit for
motor-phase failure
detection
5 1{1%}50
Function If the function is activated under C597, the controllermonitors the motor phases for failure. The
current limit value (C599)defines the threshold when a motor phase failure isindicated. The value
set under C599 corresponds to the percentage of the rated controller current [I
r
].
Activation
C597 = -0- function not active
C597 = -1- fault message TRIP
C597 = -2- warning message
Fault indication
8201BB operating module:
-TRIP: LP1
- Warning: LP1
Fieldbus:
-TRIP: 32
- Warning: 182
Important C597 and C599 are only storedinparameterset 1.