EDS84DPNET EN 4.0 - 11/2010 L 13
Communication manual 8400 protec PROFINET
Technical data
General data and operating conditions of the PROFINET
3 Technical data
3.1 General data and operating conditions of the PROFINET
3.2 Protocol data
Mounting instructions "Inverter Drives 8400 protec"
Here you can find information on general technical data, operating conditions,
and rated data of the device.
Field Values
Communication profile PROFINET
Communication medium S/FTP (Screened Foiled Twisted Pair, ISO/IEC 11801 or EN 50173), CAT 5e
Interface RJ45: Standard Ethernet (in accordance with IEEE 802.3), 100Base-TX (Fast
Ethernet) or M12-socket
Network topology Tree, star, and line
Number of nodes Max. 255 in the subnetwork
Max. cable length 100 m
PROFINET node IO device with real time (RT) communication properties
PUO ID number 0x0106
Device identification (Device ID) 0x8420
Baud rate 100 Mbps
Switching method "Store and forward"
Switch latency 125 μs at maximum telegram length
Field Values
Process data words (PCD) Max. 16 process data words (max. 32 bytes)
PROFIsafe data 4 words (8 bytes)
Acyclic parameter data channel Limited by the PROFINET frame size