Lenze Function library LenzeIO1000Drv Instrukcja Użytkownika Strona 35

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 64
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 34
DMS 1.0 EN - 07/2011 - TD05 L 35
Function library "LenzeIo1000Drv"
Function blocks
L_io1000ParCounterEPMS604 - Parameterise encoder evaluation
4.8 L_io1000ParCounterEPMS604 - Parameterise encoder evaluation
This FB serves to parameterise the I/O compound module EPM-S604. The module is an SSI
interface for direct connection to an SSI encoder.
A FALSE/TRUE edge at the bExecute input starts the parameter setting.
The dnState output shows the transmission status.
Inputs
Call possible in: ; Cyclic task
Interrupt task
; Time-controlled task (INTERVAL)
Event-controlled task (EVENT)
L_io1000ParCounterEPMS604
bExecute bDone
dwHandle dnState
byNodeAdr
byAnalogModuleNo
bDiagnosticAlarm
byDeadTime
byBaudrate
dwScaling
byBitLength
bMasterMode
bMsbFirst
bRisingEdgeSignal
bGrayCode
bSSIFunctionEnabled
Identifier/data type Information/possible settings
bExecute
BOOL
FALSEÊTRUE Start parameter setting of the analog output module
dwHandle
DWORD
9400 ServoPLC: Handle created by FB L_CanInit
Drive PLC, 9300 Servo PLC, ECS: 10
byNodeAdr
BYTE
1 ... 127 CAN node address of the I/O system
byAnalogModuleNo
BYTE
1 ... 64 Number of the analog output module
bDiagnosticAlarm
BOOL
TRUE Enable diagnostic alarm
Przeglądanie stron 34