HMI Designer
L
QN
EDBHMI-DEEN DE/EN 4.0
`çããìåáÅ~íáçå é~ê~ãÉíÉêë çÑ íÜÉ âÉóé~Ç
InthesampleprojectH310_93xx.vts the CAN adapter of the controller is the component “93xx” (slave).
This automatically declares the keypad as master.
Mark the component CAN port in the project area and select Edit Parameters to open the
Port Parameters dialog box:
Keypad declared as master Keypad declared as slave
Enter the baud rate for the controller in the Communication Parameters field.
Ó The baud rates for the 9300 Servo inverter and the 9300 Servo PLC are saved under code
C0351 (CAN bus baud rate).
After the keypad has been declared as slave:
Ó Enter a terminal address in the Terminal’s properties field. This address must not be identical
with the device address (CAN bus node address C0350 of the controller).
( 40)
Ó The settings under Sync time and Cycle time remain unchanged.
After the keypad has been declared as master:
Ó The Terminal’s properties field remains unchanged.
Confirm with OK.
qáé>
The value set under Baud rate must be identical with the setting in the controller.
If the keypad has been declared as slave, the ”Terminal address” in the Terminal’s properties
field must not be identical with the device address (CAN bus node address C0350 of the
controller).