Lenze · I/O system 1000 · commissioning guidelines for the PLC Designer · DMS 1.2 EN · 11/2012 · TD05 13
3 Establish communication
3.2 Establish a connection between L-force Controller and I/O system 1000
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4. Double-click the channel to be set as active path for control below the gateway in the
Device view.
Thus, all communication actions directly refer to this channel.
The channel currently active is displayed in bold in the Device view and marked with the
"(active)" addition:
A channel represented in italics is set as active path but has not been identified at the last
network scan.
3.2 Establish a connection between L-force Controller and I/O system 1000
For a connection via EtherCAT:
Connect the RJ45 port on the EtherCAT bus coupler module (EPM-S130) to the L-force Controller
using a network cable.
The I/O system 1000 is supplied with DC 24 V for the control electronics.
[3-1] The EtherCAT interface at the L-force Controller 3231 C
Further information can be found in the following documentation:
L-force Controller - Parameter setting & configuration