Industrial PC | Parameter setting & configuration
Parameter reference
Industrial PC extension modules
192 L 2.5 EN - 01/2012
C1581/3
C1581/4
C1581/5
Parameter | Name:
C1581/3 | ECAT master in requested state
Data type: UNSIGNED_8
Index: 22994.3
d
=
0x59D2.0x03
h
Normally, the state is requested by the PLC. For possible requested states see C1581/1 ( 191).
Value "0": Master is not in a requested state.
Value "1": Master is in a requested state.
Display range (min. value | unit | max. value)
0 1
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1581/4 | ECAT slaves in requested state
Data type: UNSIGNED_8
Index: 22994.4
d
=
0x59D2.0x04
h
Value "0": One or more slaves differ from the state requested by the master.
Value "1": All slaves have the state requested by the master.
Display range (min. value | unit | max. value)
0 1
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1581/5 | ECAT master: State information
Data type: BITFIELD_32
Index: 22994.5
d
=
0x59D2.0x05
h
Display of additional information on the current state of the master
The bits are set to value 1 if the respective states are reached.