Lenze DDS System bus CAN for PLC Instrukcja Użytkownika Strona 128

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 178
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 127
System bus (CAN) for Lenze PLC devices
FIF−CAN system blocks
8.4 FIF_CAN_Management (node number: 111)
8−5
L
PLC−Systembus EN 2.0
8.4.2 FIF_Outputs_CAN_Management
Variable Data type Signal type Address Display
code
Display
format
Notes
FIF_CAN_bResetNode_b
Bool Binary
%QX111.0.0
Carry out reset node of the FIF−CAN
FIF_CAN_bTxCan2Synchronized_b %QX111.0.1 Transmit FIF−CAN2_OUT with sync
telegram.
FIF_CAN_bTxCan3Synchronized_b %QX111.0.2 Transmit FIF−CAN_OUT with sync
telegram.
Note!
If FIF_CAN_bTxCan2Synchronized_b and/or FIF_CAN_bTxCan3Synchronized_b are integrated, it
is required to configure the device as sync transmitter. The data are transmitted immediately after
the sync telegram is sent.
8.4.3 Activating a reset node
A reset node can be activated by setting FIF_CAN_bResetNode_b to TRUE or C2458 = 1.
Tip!
Even if the FIF_CAN_Management SB has not been assigned to the control configuration, a reset
node can be activated via C2458.
(^ 5−8)
8.4.4 Defining the instant of transmission for FIF−CAN2_OUT/FIF−CAN3_OUT
Via FIF_CAN_bTxCan2Synchonized_b and FIF_CAN_bTxCan3Synchonized_b you define the
instant of transmission for the CAN objects FIF−CAN2_OUT and FIF−CAN3_OUT:
· FALSE: Data from FIF−CAN2_OUT/FIF−CAN3_OUT are sent at the end of the process image.
· TRUE: Data from FIF−CAN2_OUT/FIF−CAN3_OUT are sent to sync.
The identifiers for the sync transmission and reception telegram can be set via
C2467/C2468.
The sync Tx time can be set via C2469.
Przeglądanie stron 127
1 2 ... 123 124 125 126 127 128 129 130 131 132 133 ... 177 178

Komentarze do niniejszej Instrukcji

Brak uwag