Technical data
Rated data
7
Feldbus-Baugruppe 2113 INTERBUS
7.3
7.3.2
L
7.3-2
EDSIBS-1.0-06/2003
7.3.2 Rated data
Insulation voltages between incoming bus
and ...
Rated insulation voltage Type of insu lation
Reference earth / PE 50 V A C Mains isolation
External supply (terminal 39/59) 50 V A C Mains isolation
Power stage
820X / 821X 270 V A C Basic insulation
822X / 8200 vector 270 V A C Double insulation
93XX 270 V A C Double insulation
Control terminals
820X / 8200 vector
(with internal supply)
0VAC No mains isolation
8200 vector
(with external supply)
100 V A C Basic insulation
821X 50 V A C Mains isolation
822X 270 V A C Basic insulation
93XX 270 V A C Basic insulation
Outgoing bus (OUT) 50 V AC Mains isolation
Insulation voltages between ou tg oing bus and
...
Rated insulation voltage Type of insu lation
Earth reference / PE 50 V A C Mains isolation
External supply (terminal 39/59) 0VAC No mains isolation
Power stage
820X / 821X 270 V A C Basic insulation
822X / 8200 vector 270 V A C Double insulation
93XX 270 V A C Double insulation
Control terminals
820X / 8200 vector
(with internal supply)
0VAC No mains isolation
8200 vector
(with external supply)
100 V A C Basic insulation
821X 50 V A C Mains isolation
822X 270 V A C Basic insulation
93XX 270 V A C Basic insulation
Input bus (IN) 50 V A C Mains isolation