Data transfer
Process data signals of Lenze controllers
7
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
L
7.6-10
EDSIBS-1.0-06/2003
Control word AIF-CTRL for 82XX (Lenze code C0135, index 5F78
hex
)
Bit 820X 821x, 822x
00 = C0046 active
01 = JOG1 active in C0037
00 = C0046 active
01 = JOG1 active in C0037
,
10 = JOG2 active in C0038
11 = JOG3 active in C0039
10 = JOG2 active in C0038
11 = JOG3 active in C0039
02 CW/CCW (CW rotation/
CCW rotation)
0 = CW rotation
1 = CCW rotation
CW/CCW (CW rotation/CCW rotation) 0 = CW rotation
1 = CCW rotation
03 QSP (quick stop) 0 = QSP not active
1=QSPactive
QSP (quick stop) 0 = QSP not active
1=QSPactive
04 RFG stop (stop of the ramp function generator) 0 = RFG stop not active
1=RFGstopactive
05 RFG zero (deceleration along the T
if
ramp C0013) 0 = RFG zero not active
1=RFGzeroactive
06
Reserved
UP function for motor potentiometer 0=UPnotactive
1=UPactive
07 DOWN function for motor potentiometer 0 = DOWN not active
1 = DOWN active
08 Reserved
09 Ctrl. inhibit (controller inhibit) 0 = Controller not inhibited
1 = Controller inhibited
Ctrl. inhibit (controller inhibit) 0 = Controller not inhibited
1 = Controller inhibited
10
Reserved
11
eserve
TRIP reset 0 -> 1 = Edge from 0 to 1
12 PAR1 (Parameter set changeover) 0 -> 1 = Parameter set
1 -> 0 = Parameter set
PAR1 (Parameter set changeover) 0 -> 1 = Parameter set
1 -> 0 = Parameter set
13 Reserved Reserved
14 DC brake (DC injection brake) 0 = DC brake not active
1 = DC brake active
DC brake (DC injection brake) 0 = DC brake not active
1 = DC brake active
15 Reserved Reserved
AIF
C0046
.B15
.B13
.B14
.B12
.B0
.B1
.B2
.B3
.B4
...
...
...
.B8
.B9
.B10
.B11
QSP
CINH
TRIP-SET
TRIP-RESET
16 bits
16 bits
0
JOG/
C046
011
0101
PAR
DC
brake
CW/
CCW
2141LON010_en
Fig. 7.6-2 Access to control word and actual frequency in 82XX (fixed assignment)
Komentarze do niniejszej Instrukcji