Lenze ApplicationTemplate PackML (PLC Designer R3-x) Instrukcja Użytkownika Strona 79

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 99
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 78
Lenze · ApplicationTemplate PackML · 1.0 EN - 05/2014 79
Architecture: The ApplicationTemplate PackML in detail
Central management of alarms
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
In order to couple the Modul_1 slave module to the master again, first the reason for the alarm has
to be removed.
By means of a procedure, both state machines of master and slave module have to be
synchronised.
The deactivated slave module has to be coupled again to the state machine of the master
module using the Command_DisableModule method. Renewed coupling of machine
modules ( 72)
9.10 Central management of alarms
The alarm handling transmits all alarms that occur in the machine modules to the global Alarm List.
The state machine of the Modul_1 slave
module is decoupled automatically from the
master module. "Module Disabled" is
highlighted in red.
The state machine changes to the
"ABORTING" state.
•The Machine Control master module remains
unchanged in the "EXECUTE" state.
The machine modules forward the
messages to the Alarm List Handler.
All current alarms are visible in the
global Alarm List.
Przeglądanie stron 78
1 2 ... 74 75 76 77 78 79 80 81 82 83 84 ... 98 99

Komentarze do niniejszej Instrukcji

Brak uwag