2.0 EN - 11/2010 L 71
L-force Controls | I/O System 1000
Networking via CAN system bus
Port assignment
EPM-S620 Status word
Bit Designation Function
0– Reserved
1 PWM status 0: PWM output is stopped
1: PWM output is active
2 Output status 0: Push/pull output
1: Highside output
3 … 15 Reserved
EPM-S620 Control word
Bit Designation Function
0– Reserved
1– Reserved
2 PWM behaviour 0: Push/pull output
The output signal is activated at HIGH level and at LOW level.
•1: Highside output
The output signal is only activated at HIGH level.
3 ... 7 Output status Reserved
8 Start PWM output 0-1 edge: Starts PWM output
9 Stop PWM output 1-0 edge: Stops PWM output
10 ... 15 Reserved