Wiring of the standard device
Standard devices in the power range 55 ... 75 kW
Mains choke/mains filter assignment
5
5.7
5.7.5
5.7−6
EDSVS9332P EN 5.0−07/2013
Supply conditions
Range Description
Fuses l Only according to UL 248
l Mains short−circuit current up to 10000 A
rms
: All classes permissible
l Mains short−circuit current up to 50000 A
rms
: Only classes "J", "T" or "R"
permissible
Cables l Only in accordance with UL
l The cable cross−sections specified in the following apply under the following
conditions:
Conductor temperature < 60 °C
Ambient temperature < 40 °C
Observe all national and regional regulations!
9300 Rated fuse current Cable cross−section
Fuse L1, L2, L3, PE
Type [A] [AWG]
Operation with mains choke/mains filter
EVS9331−xP
125 1/0
EVS9332−xP 175 2/0
5.7.5 Mains choke/mains filter assignment
9300 Mains choke Interference voltage category according to EN 61800−3 and motor cable length
Component Component
Type C2 max. [m] C1 max. [m]
EVS9331−xP ELN3−0027H105
EZN3A0022H150 25 E82ZN75334B230 10
E82ZN75334B230 50 EZN3B0022H150 50
EVS9332−xP ELN3−0022H130
EZN3A0022H150 25 E82ZN75334B230 10
E82ZN75334B230 50 EZN3B0022H150 50
Installation to UL