Configuration
Basic configurations
8
8.5
8.5−9
EDSVS9332P EN 5.0−07/2013
IMPORTANTPossible settingsCode
SelectionLenzeDesignationNo.
C0120 OC6 LIMIT 0 00 {1 %} 120 Threshold for the I
2
× t
monitoring of the motor
l C0120 = 0: I
2
× t monitoring
switched off
l I
2
× t > C0120 ð TRIP OC6
C0121 OH7 LIMIT 150 45 {1 °C} 150 Temperature for OH7
Threshold for motor
temperature warning
C0122 OH4 LIMIT 85 45 {1 °C} 85 Temperature for OH4
Threshold for heatsink
temperature warning
C0125 BAUD RATE 0 0
1
2
3
4
9600 baud
4800 baud
2400 baud
1200 baud
19200 baud
LECOM baud rate
LECOM baud rate for 2102
communication module
C0126 MONIT CE0 3 0
2
3
TRIP
Warning
Off
CE0monitoring
Configuration of
communication error
monitoring with CE0
automation interface
C0127 OC8 LIMIT 0 0 {1 %} 120 Threshold for the I
2
× t advance
warning of the motor
l C0127 = 0: I
2
× t warning
switched off
l I
2
× t > C0127 ð fault
message OC8 (response set
in C0606)
C0128 TAU MOTOR 5.0 0.1 {0.1 min} 50.0 Thermal time constant of the
motor
The time constant is required
for calculating the I
2
× t
disconnection.
C0130 ACT TI ) NSET
Active T
i
times of NSET
See system
manual
(extension)
C0134 RFG CHARAC 0 0
1
Linear
S−shaped
NSET
Ramp function generator
characteristic for main setpoint
C0135 CONTROL
WORD
0 0 {1} 65535 LECOM control word
Device control word for
LECOM−A/B/LI or keypad
See system
manual
(extension)
C0136
)
LECOM control word
See system
manual
(extension)
1 CTRLWORD
C135
Control word in DCTRL
2 CTRLWORD
CAN
Control word in CAN−IN
3 CTRLWORD AIF Control word in AIF−IN
C0141 FCODE
(SETVAL)
0.0 −199.9 {0.1 %} 199.9 Main setpoint
Freely configurable code for
relative analog signals
l Used as main setpoint in
configurations C0005 = xxx1
C0142 START
OPTIONS
1 0
1
Start lock
Auto start
Start option
Start conditions are executed:
l After mains connection
l After message (t > 0.5s)
l After
TRIP