6.3 Communication function parameters
6.3.1 FB90 (FB DRIVE)
Function block
For every drive one instance is to be created.
The function block is based on the functions SFC14/15.
Parameters Data type Possible values/meaning
Tag IN: STRING Special identifier; do not change
PB_Address IN: BYTE 0...31 PROFIBUS address of the drive (hexadecimal)
Address1=1,address15=F
EA_Address IN: INT I/O address of the drive (decimal)
DriveServer_DB IN: BLOCK_DB Data block with parameter data job list via OPC
e.g. DB80
DrivePar_DB IN: BLOCK_DB Data block with parameter data job list of the PLC
e.g. DB81
TimerNo IN: TIMER Timer for monitoring the drive
e.g. T1
TimeOut IN: S5TIME Timeout for monitoring.
If not indicated, pre-setting ”S5T#1S” (= 1 s) is used.
Busy OUT: BYTE
Status of the function:
u
s
y
O
U
0x00 Not active (jobs ha v e been processed)
0x01 Active (jobs are still being processed)
0x10 Incorrect identifier in the data block, incorrect data block
indicated or overwritten: Reload data block
0x11 PB_Address incorrect (permissible values: 1 ... 123)
0x40 Count outside the range 0 ... 31
0xF0 No module c onfigured under PB_Address
0xF1 Length of s ource range <> Length o f configured user
data
0xFF General I/O access error