8.6 Code table
Drive PLC
Appendix
8−22
L
DrivePLC DE 6.0
Code InfoPossible settingsLCDCode Info
SelectionLenze
LCD
C0362 Sync cycle
g
System bus: Time between two sync telegrams
1 {1 ms} 30
C0363 Sync corr 1 System bus: Sync correction increments
1 0.4 s/ms
2 0.8 s/ms
3 1.2 s/ms
4 1.6 s/ms
5 2.0 s/ms
C0365 DIS:CAN active
g
Input signal CAN active
0 CAN not active
1 CAN active
C0366 Sync response 1 System bus: Sync response
0 No response
1 Response to sync
No response
PLC responds to a sync telegram by sending the
CAN1_OUT object.
C0367 Sync Rx Id 128 System bus: Sync Rx identifier
Receive identifier of the Sync telegram.
1 {1} 256
C0368 Sync Tx Id 128 System bus: Sync Tx identifier
Send identifier of the sync telegram.
1 {1} 256
C0369 Sync Tx time 0 System bus: CAN sync send telegram cycle
A sync telegram with the identifier of C0368 is sent
with the set cycle time.
0 {1} 65000
0 = off
C0370 Gateway addr. 0 System bus: Activate SDO gateway remote parameterisa-
tion
The SDO gateway cannot be used to read out codes
>C2000 or codes of the Inverter Drives 8400 and Servo
Drives 9400.
When selecting a setting 0, all code read/write acces-
ses will be redirected to the system bus device with the
corresponding node address.
The codes are accessed via the SDO1 parameter chan-
nel of the target device. The source or target of the
code accesses is defined in C0371.
0 {1} 63
0 = remote parameter setting deactivated
C0371 Gateway channel 1 System bus: Sync response
1 On board CAN
2 FIF CAN
Selection 1 (on board CAN): Parameter settings made
via AIF or FIF−CAN are transferred to the on board CAN
interface. For remote parameterisation, C0370 must be
non−zero.
Selection 2 (on board CAN): Parameter settings made
via AIF or FIF−CAN are transferred to the FIF CAN inter-
face. For remote parameterisation, C0370 must be
non−zero.
C0372 FIF module Id
g
FIF module HW identification
0 No module
1 Standard I/O
2 System bus (CAN)
6 Intelligent module
10 No valid identification
C0373 EB module Id
g
Extension board HW identification
0 No module
1 Standard module (extension board 1)
10 No valid identification