Drive PLC
System blocks
2.6 ANALOG1_IO (node number 11)
2−21
L
DrivePLC DE 6.0
2.6.2 Outputs_ANALOG1 (analog output)
You can use this SB as a monitor output. You can output internal analog signals via
terminal AOV as voltage signals and
terminal AOI as current signals
and use them, e.g. as display or setpoint values for following drives.
AOV
A
AOUT1_nOut_a
Outputs_ANALOG1
C0434
AOI
Fig. 2−11 Outputs_ANALOG1
System variables
Variable Data type Signal type Address Display
code
Display
format
Notes
AOUT1_nOut_a Integer analog %QW11.0 C0434 dec [%] Analog output 1
Function
A voltage of 10 V is output at terminal AOV, if the signal on AOUT1_nOut_a = 16384 = 100 %
A current of 20 mA is output at terminal AOI, if the signal on AOUT1_nOut_a = 16384 = 100 %
Terminal assignment
Terminal Use Data
AOV Analog output 1 (voltage signal) Level:
Resolution:
Normalisation:
−10 V ... +10 V (max. 2 mA)
10 bits + sign
10 V 16384 100 %
AOI Analog output 1 (current signal) Level:
Resolution:
Normalisation:
−20 mA ... +20 mA
10 bits + sign
20 mA 16384 100 %
A Internal ground, GND −