8.1 PLC functionality
8−1
L
DrivePLC DE 6.0
8 Appendix
8.1 PLC functionality
Field Number Description
Inputs
digital 8 Free inputs (3 of them interruptible) 24 V DC / 8 mA each input
analog 3 Free inputs (10 bit + sign) 10 V
Outputs
digital 4 Free outputs 24 V DC / max. 1 A each output
analog 1 Free output (10 bit + sign) 10 V / max. 2 mA
Operation set According to IEC61131−3
Counter/times According to IEC61131−3, depending on the data memory available.
Flags 1000 Flag words
Memory See chapter 8.3 (^ 8−4)
Processing time (1−bit operation) 1 s
Task types
8 Time or event−controlled tasks (1 ms ... 16 s)
1 Cyclic task
Programming software Drive PLC Developer Studio
Programming languages according to IEC61131−3 standard (IL, LD, FBD, ST,
SFC) as well as CFC editor
Monitoring, visualisation, simulation and debugging