7.3 DFIN_IO_DigitalFrequency (node number 21)
Drive PLC
System blocks − Extension Board 3
7−8
L
DrivePLC DE 6.0
Tip!
You can connect incremental encoders with HTL level that supply signals A and B only, to PIN 2 and
PIN 9. The inputs at PIN 3 and PIN 1 must then be connected to the supply voltage of the incremental
encoder.
The connection is as shown in the figures:
Use twisted pair cables and screened pair cables.
Connect the screen at both ends.
Do not change the cable cross−sections indicated.
7.3.1.3 Touch probe (TP)
Process: The current angle value (encoder input value) is saved by a quick interrupt in the operating
system when a signal changes at the TP activating input (e.g. X3/I1).
DFIN_dnIncLastScan_p
TP
j
Fig. 7−8 Function chart of a TP
Time−equidistant start of an interval task
Phase−angle signal
Touch probe configuration
Code LCD
Possible settings
IMPORTANT
Lenze Selection
C0428 DFIN TP sel. 0 Touch probe selection
0 Touch probe via zero pulse
1 Touch probe via digital input X3/I1
C0429 TP delay 0 Touch probe delay
Compensation of delay times
of TP signal source at X3/I1
−32767 {1 inc} 32767
C0431 DFIN TP EDGE 0 Touch probe activation
For touch probe via digital
input X3/I1
(C0428 = 1)
0 Activation with positive signal
1 Activation with negative signal