2.12 DCTRL_DriveControl (node number 121)
Drive PLC
System blocks
2−32
L
DrivePLC DE 6.0
2.12.1 Inputs_DCTRL
System variables
Variable Data type Signal type Address
Display
code
Display
format
Notes
DCTRL_bFail_b Bool binary %IX121.0.0
Status word bit−coded
TRUE = Error active
DCTRL_bTrip_b Bool binary %IX121.0.2
Status word bit−coded
TRUE = Error active (TRIP or FQSP
active)
DCTRL_bWarn_b Bool binary %IX121.0.12
Status word bit−coded
TRUE = Warning active
DCTRL_bMeld_b Bool binary %IX121.0.13
Status word bit−coded
TRUE = Message active
DCTRL_bExternalFault
_b
Bool binary %IX121.0.15
Status word bit−coded
TRUE = External error
DCTRL_wStat WORD %IW121.0
Status word with device status
(bit 8 ... 11, see below)
DCTRL_wFaultNumbe
r
WORD %IW121.2 Error number from C0168
Tip!
Unlike ECS and SPLC, the binary signals of the SB DCTRL are on DCTRL_wStat!
Device status: Bits 8 ...11 of DCTRL_wStat show the DrivePLC status binary coded:
DCTRL_wStat.11 DCTRL_wStat.10 DCTRL_wStat.9 DCTRL_wStat.8 Notes
0 0 0 0
Initialisation after connection of the supply
voltage
0 1 1 0 Normal operation
0 1 1 1
The activation of a monitoring function led to a
warning or message (FQSP)
1 0 0 0
The activation of a monitoring function led to a
TRIP