Fault reset
The current fault can be reset by a TRIP−RESET e.g. via C0043:
Code LCD
Possible settings
Info
Lenze Selection
C0043 Trip reset 0 TRIP reset
0 TRIP−RESET (current TRIP reset)
1 Error occurred (TRIP is active)
Deleting entries in the fault memory
The entries in the fault memory can be deleted via C0167.
This function can only be used if there is no active fault.
Code LCD
Possible settings
Info
Lenze Selection
C0167 Reset failmem 0 Reset fault memory
0 No function
1 Delete all entries in history buffer
Access to fault memory via Global Drive Control (GDC)
The fault memory of the PLC can also be displayed in the GDC.
Double−click on "Dialog diagnostics" in the GDC parameter menu to open the 9300
diagnostics dialog box:
History buffer
No. of system error message and response (C0168/x)
Time of occurrence (C0169/x)
Frequency of successive occurrence (C0170/x)
Reset of the fault (TRIP−RESET); only possible if there is no active fault.