Lenze E84AYCET EtherCAT MCI module Instrukcja Użytkownika Strona 43

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 109
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 42
Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17 43
6 Commissioning
6.5 Establishing an online connection with the »Engineer«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.5.2 Gateway Controller -> configure EtherCAT ADS (Beckhoff)
The Gateway EtherCAT ADS bus connection makes it possible to establish an online connection to a
Lenze inverter that is connected to a Beckhoff Controller via EtherCAT (gateway function).
[6-3] Example: EtherCAT bus system with a Beckhoff Controller as Gateway
How to configure an online connection to a field device which is connected to a Beckhoff
Controller via EtherCAT:
1. Highlight the project root in the project.
Alternatively: Create a new project or carry out a fieldbus scan.
2. Execute the menu command Insert Insert device detected online.
3. Select Gateway Controller -> EtherCAT ADS as bus connection.
4. Configure access data:
Configure the access data applicable to the Controller via the Insert address button.
•The Search button initiates the Controller to display the fieldbus nodes connected to the
EtherCAT segment.
Przeglądanie stron 42
1 2 ... 38 39 40 41 42 43 44 45 46 47 48 ... 108 109

Komentarze do niniejszej Instrukcji

Brak uwag