Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17 95
12 Error messages
12.2 Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Operational status quit [0x01bc8131]
Sync telegram failure [0x01bc8700]
Response (Lenze setting printed in bold) Setting: C13880/1 (; Adjustable response)
: None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
The EtherCAT data exchange was stopped in the
"Operational" state.
See also chapter "Interruption of EtherCAT
communication" ( 82).
• Check cables and terminals.
The master has to reset the node to the "Operational"
status. (If required, check a pending emergency
message first).
Response (Lenze setting printed in bold) Setting: C13880/2 (; Adjustable response)
: None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
• The cycle time settings are faulty.
The task time setting of a linked PLC program is faulty.
• EtherCAT master / DC master settings are incorrect.
• The sync source setting is faulty.
• Check the cycle times.
• Check the task time of a linked PLC program.
• Check the EtherCAT master / DC master settings.
• Check the settings in C01120
of the standard device
(selection of the sync source).