6 Commissioning
6.5 Establishing an online connection with the »Engineer«
44
Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
How to use the EtherCAT ADS communication path:
1. Highlight the desired inverter, to which a gateway connection via EtherCAT ADS is to be
established, in the project tree.
2. Call the menu command Online Set communication path and go online.
3. Select Gateway Controller -> EtherCAT ADS as bus connection.
4. Enter the access data applicable to the Controller in area .
Enter the user name, password, and the IP address and the AMS Net ID of the EtherCAT
interface of the Controller.
5. In area , specify the EtherCAT address of the field device to which the online connection
is to be established.
Alternatively you can click the Search/Enter button which calls the Select Device Access Path
dialog window. By this, the »Engineer« initiates the Controller to display the devices
detected on the EtherCAT segment.