Lenze CANopen Controller-based Automation Instrukcja Użytkownika Strona 22

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 110
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 21
Lenze · Controller-based Automation · CANopen® Communication Manual · DMS 6.3 EN · 04/2014 · TD17 22
5Technical data
5.4 Bus cable length
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.4 Bus cable length
5.4.1 Total cable length
The total cable length is also specified by the baud rate.
5.4.2 Segment cable length
Repeaters divide the total cable length into segments. The segment cable length is defined by the
cable cross-section and the number of nodes per segment. Without a repeater, the segment cable
length corresponds to the total cable length.
Note!
It is absolutely necessary to comply with the permissible cable lengths.
Observe the reduction of the total cable length due to the signal delay of the repeater.
Use of repeaters
( 23)
If the total cable lengths of the nodes are different at the same baud rate, the smaller
value must be used to determine the max. cable length.
Baud rate [kbps] Max. bus length [m]
Servo Drives
9400
Inverter Drives
8400
I/O-System 1000
(EPM-Sxxx)
CANopen bus coupler
10 8000 - 5000
20 4000 - 2500
50 1500 1500 1000
125 600 600 500
250 275 275 250
500 110 110 80
1000 13 13 25
Max. number of
nodes per segment
Cable cross-section
0.25 mm
2
0.50 mm
2
0.75 mm
2
1.00 mm
2
2 240 m 430 m 650 m 940 m
5 230 m 420 m 640 m 920 m
10 230 m 410 m 620 m 900 m
20 210 m 390 m 580 m 850 m
32 200 m 360 m 550 m 800 m
63 170 m 310 m 470 m 690 m
100 150 m 270 m 410 m 600 m
Przeglądanie stron 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 109 110

Komentarze do niniejszej Instrukcji

Brak uwag