8.3.4 Alarm groups
Alarm groups are used for organizing the available alarms. Each alarm is definitely
assigned to right one alarm group and is managed by this group. All alarms of a group
can get assigned a common deactivation variable and common parameters regarding
the alarm saving. Regard that even a single alarm must be configured within an alarm
group.
A hierarchical structure of alarm groups can be defined via Folder elements. When a
alarm group is selected in the configuration tree, automatically the dialog Alarm
group will be displayed:
Configuration dialog Alarm group
In the field Description you can enter a name for the alarm group.
As Deactivation variable a boolean project variable can be defined. At a rising edge on
this variable the alarm creation for all alarms of the group will be deactivate, at a
falling edge it will be re-activated.
Via button Add an alarm can be added to the group. A new line in the table window
will be inserted and there the following parameters are to be set:
Expression: Enter here the project variable or an expression (e.g. "a + b") to which the
alarm should refer. It is recommended to use the input assistant <F2> resp. the
"Intellisense" function for an correct entry.