L-force | PLC Designer
Siemens Import
554 DMS 3.2 EN 02/2011 TD29
The only exception or limitation for conversion is related to resetting timers which can
be done in STEP5 but not normally in IEC 61131-3.
The individual convertible commands:
U, UN, O, ON, S, R, = with the following bit operands: I (inputs), O (outputs), M
(memory locations), S (S memory locations), D (Data in data blocks)
U, UN, O, ON with the following operands: T (Timer), C (Counter)
S, R with the following operands: C
SU, RU, P, PN with the following operands: E, A, M, D
O, O(, U(, )
L, T with the following operand ranges: E, A, M, D, T, C, P (Periphery) and operand
sizes: B (byte), W (word), D (double word), L (left byte), R (right byte)
L with the following constant formats: DH, KB, KF, KH, KM, KT, KZ, KY, KG, KC
SI, SE, SA with the following operands: T
ZV, ZR with the following operands: C
+, -, X, : with the following operands: F (fixed point number), G (floating point
number)
+, - with the following operands: D (32 bit fixed point number)
!=, ><, >, <, >=, <= with the following operands: F, D, G
ADD with the following operands: BF, KF, DH
SPA, SPB with the following operands: PB, FB (with most parameter types), SB
A, AX with the following operands: DB, DX
BE, BEA, BEB
BLD, NOP, ***
UW, OW, XOW
KEW, KZW, KZD
SLW, SRW, SLD, RRD, RLD
SPA=, SPB=
SPZ=, SPN=, SPP=, SPM=
TAK
D, I
Most of the formal operand commands