9400 HighLine | Parameter setting & configuration
Basic drive functions
Limiter | Parameter setting
206 Firmware 1.37 - 09/2006 L
Response if limit values are exceeded
When the limit values are switched effectively and a set limit value is exceeded, the
following reactions occur:
r The setpoints of the active basic function ("Manual jog
", "Homing" or "Positioning") are
changed (limited).
r Via the output LIM_dnState of the SB LS_Limiter
a corresponding status is output.
r The display parameter C02714
is set to "1" ("limitation is active").
r The response parameterised in C02716/3
is activated (Lenze setting: "No response").