9400 HighLine | Parameter setting & configuration
TAs for interconnection via electrical shaft
TA "Electronic gearbox" | Selection of master value source and output
306 Firmware 1.37 - 09/2006 L
12.2.4.1 Master value source: Virtual master
If the "Virtual master" is selected as master value source, the master value is created in the
TA and transmitted via a bus system or the digital frequency output to the other slave
drives.
r Parameter setting: Tab Application parameter Dialog level Overview Virtual
master
r Configuration: Tab FB editor FB VirtualMaster
Parameters Lenze setting
Value Unit
C03565 Operating mode Continuous operation
C03568/1 Master speed 1 500.0000 Unit/t
C03568/2 Master speed 2 0.1000 Unit/t
C03569/1 Speed inching right 50.0000 Unit/t
C03569/2 Speed inching left 25.0000 Unit/t
C03570/1 Inching ramp 0.010 s
C03570/2 Continuous operation ramp 1.000 s
C03570/3 Stop ramp 1.000 s
Control/setpoint inputs of the function Signal configuration
Lenze setting Control/setpoint input (Multiplexer parameters)
FALSE VMas master shaft STOP1 C03058/1
C03016 Activate master function C03058/3
C03017 VMas inching positive C03058/4
C03018 VMas inching negative C03058/5
FALSE VMas start continuous operation C03058/7
FALSE VMas 2. master speed C03058/8
0 VMaster handwheel C03056