9400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00002
544 Firmware 1.37 - 09/2006 L
C00002
Parameter | Name:
C00002 | Controller commands
Data type: UNSIGNED_32
Index: 24573
d
= 5FFD
h
Controller commands
C00003
shows the status of the last executed controller command.
•Under C00150
you can query the current status of the device control.
Selection list
(Lenze setting printed in bold) Information
0 Load Lenze setting Resets parameters to Lenze setting.
Only possible when the application has stopped and
the controller is inhibited.
1 Load start parameters Loads parameters from the memory module.
Only possible when the application has stopped and
the controller is inhibited.
5 Activate application Activates the application selected under C00005
.
If the application is also started, depends on the auto-
start setting selected.
Only possible when the application has stopped.
7 Save selected application Selects the active application as start application.
11 Save start parameters Saves parameters fail-safe in the memory module.
20 Delete logbook Deletes all logbook entries.
21 Archive log file Exports logbook entries to file.
31 Start application
32 Stop application
33 Reset program Executes a reset
All variables except for the RETAIN variables are reset
to their initialisation value.
The situation corresponds to a power failure or
deactivation/activation of the controller (warm start)
while the program is running.
34 Delete program Executes a reset (original)
All variables including RETAIN and PERSISTENT
variables are reset to their initialisation value.
The application program is deleted and the controller
is reset to its original status.
35 Restart program Executes a reset (warm start)
All variables except for the PERSISTENT variables are
reset to their initialisation value.
The situation corresponds to the start of a new
program loaded into the control (cold start).
36 Reset runtime measurement
41 Inhibit controller
42 Enable controller
43 Reset error
45 Activate quick stop "Basic functionQuick stop
"
46 Quick stop reset "Basic functionQuick stop
"
47 Internal command 47 For Lenze service only
48 Internal command 48 For Lenze service only