9400 HighLine | Parameter setting & configuration
Motor interface
Initial commissioning | Display/edit motor data in the »Engineer«
68 Firmware 1.37 - 09/2006 L
Overview of motor data
Parameters Information Lenze setting
Value Unit
C00006 Motor control selection Servo control with synchronous
motor
C00059 Motor - number of pole pairs -
C00074 Feedforward control of current controller Deactivated
C00075
Current controller gain 28.66 V/A
C00076
Current controller reset time 1.50 ms
C00077
Field controller gain 165.84 A/Vs
C00078
Field controller reset time 15.1 ms
C00079 Motor - mutual inductance - mH
C00081
Motor - rated power 1 kW
C00082 Motor - rotor resistance - Ohm
C00083 Motor - rotor time constant - MS
C00084
Motor stator resistance 19.8000 Ohm
C00085
Motor stator leakage induct. 30.500 mH
C00087
Rated motor speed 4000 rpm
C00088
Rated motor current 0.9 A
C00089
Rated motor frequency 200 Hz
C00090
Rated motor voltage 245 V
C00091
Motor - cosine phi 1.00
C00092 Motor - magnetising current - A
C00128/1
Therm. time constant coil 1.0 min
C00128/2
Therm. time constant plates 5.0 min
C00186 ENP: Identified motor type -
C00187 ENP: Identified serial number -
C00188 ENP: Status -
C00577
Field weakening controller gain 0.000 Vs/V
C00578
Field weakening controller reset time 2000.0 ms
C01190
Motor thermal sensor KTY83-110
C01191/1
Temperature for spec. characteristic 25 °C
C01191/2
Temperature for spec. characteristic 150 °C
C01192/1
Resistor for spec. characteristic 1000 Ohm
C01192/2
Resistor for spec. characteristic 2225 Ohm
Highlighted in grey = display parameter
Note!
If the motor has been selected via the »Engineer« motor catalog or if the motor
data have been adapted offline in the »Engineer«, all motor data must be
transferred to the controller with an established online connection and stored
with mains failure protection in the memory module (C00002
= "11").