Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37 Instrukcja Użytkownika Strona 554

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 679
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 553
9400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00105
554 Firmware 1.37 - 09/2006 L
C00105
C00106
C00107
C00114
C00118
Parameter | Name:
C00105 | Quick stop decel. time
Data type: UNSIGNED_32
Index: 24470
d
= 5F96
h
Time between quick stop activation and standstill plus relative inaccuracy time (C00106).
"Basic functionQuick stop
"
Setting range
(min. value | unit | max. value) Lenze setting
0.000 s 999.999 0.000 s
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000
Parameter | Name:
C00106 | Quick stop S-ramp time
Data type: UNSIGNED_32
Index: 24469
d
= 5F95
h
S-ramp time in [%] referred to the deceleration time set under C00105.
"Basic functionQuick stop
"
Setting range
(min. value | unit | max. value) Lenze setting
0.00 % 100.00 0.00 %
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00107 | Ref. quick stop decel. time
Data type: UNSIGNED_8
Index: 24468
d
= 5F94
h
Reference for the deceleration time set in C00105.
"Basic functionQuick stop
"
Selection list
(Lenze setting printed in bold)
0 Reference = reference speed
(C00011)
1 Ref. = Current speed
; Read access ; Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00114 | DIx terminal polarity
Data type: UNSIGNED_8
Index: 24461
d
= 5F8D
h
"0" = positive logic (HIGH level = TRUE, LOW level = FALSE)
"1" = negative logic (HIGH level = FALSE, LOW level = TRUE)
Setting range
(min. value | unit | max. value)
01
Subcodes Lenze setting Information
C00114/1 0 Terminal polarity of digital inputs 1 ... 8
C00114/...
C00114/8
; Read access ; Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00118 | DOx terminal polarity
Data type: UNSIGNED_8
Index: 24457
d
= 5F89
h
"0" positive logic (TRUE HIGH level, FALSE LOW level)
"1" negative logic (FALSE HIGH level, TRUE LOW level)
Setting range
(min. value | unit | max. value)
01
Subcodes Lenze setting Information
C00118/1 0 Terminal polarity of digital outputs 1 ... 4
C00118/...
C00118/4
; Read access ; Write access CINH PLC STOP No transfer COM MOT
Przeglądanie stron 553
1 2 ... 549 550 551 552 553 554 555 556 557 558 559 ... 678 679

Komentarze do niniejszej Instrukcji

Brak uwag